DigiTemp 2

  • Digital mixing valve with integrated connectivity
  • Four models: 23, 55, 71 and 125 GPM (@10psid)
  • Light and heavy‑duty commercial applications

“nexaplatform

Technical Documents

Frequently Asked Questions


What is DigiTemp 2?

DigiTemp 2 is a digital water mixing valve designed for precise control of domestic hot water temperature in commercial and institutional systems. It delivers ±2°F accuracy, meets ASSE 1017 standards, and provides advanced connectivity to support safety and performance.

What is the difference between DigiTemp 2 and DigiTemp 2S?

DigiTemp 2 is available as a standalone valve or as a factory pre-piped packaged system. DigiTemp 2S is the packaged version and uses the same control platform while reducing field labor and providing additional system integration and sensing.

Does DigiTemp 2 support building automation systems?

Yes. DigiTemp 2 supports BACnet MSTP and Modbus protocols for integration with building automation systems. This allows users to monitor and control system performance through connected building management platforms.

What is the temperature range and accuracy of DigiTemp 2?

DigiTemp 2 has an adjustable setpoint range of 60°F to 180°F and maintains temperature within ±2°F. The system complies with ASSE 1017 requirements for commercial hot water applications.

What safety features are included with DigiTemp 2?

DigiTemp 2 includes a high-temperature sanitization mode to address bacteria, delivers full cold water flow during power loss, and incorporates check valves to help prevent cross-flow. The system also supports alerts and secure access control.

What is “Works with Nexa” and how does it benefit users?

“Works with Nexa” provides cloud-based monitoring and control capabilities. Users can view system performance, receive alerts, log operating data, adjust temperatures remotely, and manage multiple sites through secure user access.

Where is DigiTemp 2 typically used?

DigiTemp 2 is commonly installed in commercial and institutional facilities where precise temperature control and hot water safety are important. Typical applications include healthcare, hospitality, education, corrections, and multi-building campus environments.